Onicon F-3100 Series Manuale Utente Pagina 28

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 41
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 27
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
F-3100 Flow Meter Manual 06/14 - 0670-7 Page 28
0516
Remove retaining screw to
expose connector.
(Shown with High Voltage)
Power connections
are under this cover.
Pulse Out 1
Pin 16 - Pos (+)
Pin 17 - Neg (-)
Pulse Out 2
Pin 18 - Pos (+)
Pin 19 - Neg (-)
4-20 mA Output
Pin 9 - Pos (+)
Pin 10 - Neg (-)
5-15-08
SIGNAL CONNECTIONS
POWER CONNECTIONS
Step 1: Loosen screws to lift cover. Step 2: Lift cover to expose electrical connections.
Step 3: Make SIGNAL connections as shown
Pull straight out on connectors to remove them.
Step 4: Open cover to expose POWER Connections.
Opto-coupled open collector pulse outputs
Maximum voltage: 40VDC
Maximum current: 100mA
Maximum saturation voltage collector/emitter @ 100mA: 3 VDC
Pulse Output 1 / Pulse Output 2
Vedere la pagina 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 40 41

Commenti su questo manuale

Nessun commento