SECTION 4.0: START-UP & COMMISSIONING FOR ONICON
INSERTION THERMAL MASS FLOW METERS
4.1 HELPFUL HINTS FOR START-UP & COMMISSIONING
A step-by-step procedure and companion worksheet are located on the next two pages. Please
read all installation instructions carefully before proceeding with start-up and commissioning.
Please read these helpful hints before proceeding with the start-up and commissioning procedure
on the next page.
1. ONICON ow meters are individually calibrated for a particular application. Be sure to
verify the pipe size and location.
2. When measuring analog output signals, remember that current (mA) must be measured
in series, while voltage is measured in parallel. If the 4-20 mA signal is already connected
to a control system, you must break the connection and measure the signal in series.
3. Do not attempt to rotate the electronics enclosure on the stem.
4. Do not connect power to the analog output without rst conrming that it is congured for
loop powered operation. See section 3.5.2.